KYN44-12 indoor type alternating-current metal-clad mid-set withdrawable switchgear is applicable for three-phase power systems of AC50Hz and 3.6~12kV, used for electric energy receiving and distribution, is a PTD control device for single-bus segment systems. It is mainly used in power plants and substations for power transmission, and industrial and mining enterprises for power distribution, as well as secondary substations for power receiving and transmission and starting of large high-voltage motors, etc, realizes control, protection and monitoring.
● Fully compatible with technical performances and schemes of KYN28A-12, GZS and other switchgears.
● More mechanical interlocking protection and operation characteristics.
● Complete mechanical interlocking protection and operation characteristics.
● A variety of configurations of vacuum circuit breakers.
● w-vac vacuum circuit breaker from Westing House Corporation.
● VD4 vacuum circuit breaker from ABB Corporation.
● 3AH5 vacuum circuit breaker from SIEMENS.
● 10-VPR vacuum circuit breaker from MITSUBISHI.
● ZN28GE and VB2 vacuum circuit breakers from GE.
● EV12 vacuum circuit breaker from Merlin Gerin.
● VS1 vacuum circuit breaker from Senyuan Corporation.
● All kinds of homemade vacuum circuit breakers such as VS1, ZN28, ZN63, ZN, etc.
● Adoption of imported and homemade microcomputer-based monitor and remote controller, or electromechanical relay protection and meter monitoring.
● Luxurious imported type, universal type and economical type for option.
Outline dimension of switchgear (mm)
Breaker model
|
W-VAC
|
VPR
|
3AH5
|
VD4、VS1、ZN28、ZN63
|
Height (H)
|
2300
|
2300
|
2300
|
2300
|
Width (W)
|
≤1250A>1600-3150A
|
700
800
|
800
1000
|
800
1000
|
800
1000
|
Depth (D)
|
1660
|
1660
|
1600
|
1500 (Note 2)
|
Note: 1. Cabinet width is 800 except the breaker cabinet whose width varies.
2. Depth of incoming/outgoing cables is 1660.
Main technical parameters of switchgear
Item
|
Unit
|
Data
|
Rated voltage
|
KV
|
3.6,7.2,12
|
Rated insulation level
|
1min power frequency withstand voltage
Lightning impulse voltage (full wave)
|
KV
KV
|
24,32,42
40,60,75
|
Rated frequency
Rated current
Rated current of main bus
Rated current of branch bus
4s short-time withstand current (effective value)
Rated peak withstand current (peak)
|
Hz
A
A
A
KA
KA
|
|
50
5-3150
1600,2000,2500,3150
630,1250,1600,2000,2500,3150
16,20,25,31.5,40,50
40,50,63,80,100,125
|
Protection class
|
|
The shell is IP4X, and it is IP2X when the circuit breaker chamber door is opened
|
Note: please take the breaker model into consideration especially for short-circuit capacity of current transformer.
Corporation
|
C-H
|
ABB
|
SIEMENS
|
GE
|
Mitsubishi
|
Homemade
|
Model
|
W-VAC
|
Vd4
|
3AH5
|
ZN28GE、VB2
|
VPR
|
VS1、ZN28、ZN63…
|