ZW32-40.5/1600-25
outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker is
mainly composed of integrated solid-sealed pole, current transformer, operating
mechanism and cabinet. An isolating switch can be installed. This type of
circuit breaker has a miniaturized design, and the shell is made of
high-quality steel box. The current transformer can be selected according to
user needs.
The
device is mainly used in medium-voltage overhead line power grids for dividing
and combining load current, overload current and short-circuit current.
Ambient
air temperature: -30°C ~+60°C;
Altitude:≤
3000 meters;
The
wind speed:≤ 34m/s;
Vibration
or ground movement from the outside of the switchgear cell system can be
ignored;
Pollution
level: Level IV;
Storage
temperature -40°C ~+85°C.
Item |
Unit |
Specification |
Rate voltage |
kV |
40.5 |
Rate current |
A |
1250/1600 |
Rate frequency |
Hz |
50 & 60 |
Power frequency withstand voltage (dry) (wet),ground/fracture |
kV |
80 95/95 |
Lightning impulse withstand current (peak) phase to phase,ground/fracture |
kV |
185 |
Rated short-circuit breaking current |
kA |
25/31.5 |
Rated short-circuit making current (peak) |
kA |
63/80 |
Rated peak withstand current |
kA |
63/80 |
Short-time withstand current,4S |
kA |
25/31.5 |
Rated operating cycle |
|
O-0.1s -CO-3s -CO-6s CO-60s Recover |
Rated short-circuit current breaking times |
times |
30 |
Mechanical life |
times |
10000 |
Mechanism control voltage |
V |
AC/DC220 |
Power frequency withstand voltage of secondary circuit (1min ) |
kV |
2 |
Item |
Unit |
Specification |
Contact stroke |
mm |
16±1 |
Contact over-travel |
mm |
4±0.5 |
Opening speed |
m/s |
1.4-1.8 |
Closing speed |
m/s |
0.4-0.8 |
Contact closing bouncing duration |
ms |
≤5 |
Center distance between phases |
mm |
460±2 |
Opening/Closing synchronism between poles |
ms |
≤2 |
Conductive loop resistance of each phase |
μΩ
|
< 80 |
Closing time |
ms |
≤100 |
Opening time |
ms |
≤50 |
Weight |
Kg |
270 |